Thermal storage
Water Tanks
Thermal energy storage, buffer, commercial hot water (calorifier), indirect and boiler feedwater tanks.

Overview
About Water Tanks
We supply thermal energy storage tanks, buffer tanks, commercial direct hot water tanks (calorifiers), commercial indirect water tanks and boiler feedwater tanks.
No two projects are the same, so our engineering, manufacturing and supply processes are designed to minimise lead times from initial specification to delivery. Alongside the tanks we provide 3D and 2D CAD design support, tank selection, and custom skid packages with pumps, controls, tanks and integrated heat transfer equipment.
Tanks are configured by construction (plastic, stainless steel or enamel), capacity, heating circuit, pressurised or vented cylinder, and heat recovery — so the vessel suits the multi-energy system it serves.
High-performance enamel liner
Enamel-lined storage tanks backed by decades of expertise in glaze technology.
Corrosion protection
A 1.8-metre magnesium anode rod protects against corrosion, scaling and hot water erosion for extended service life.
80 mm insulation
Integral polyurethane foam insulation for heat retention, extended standby time and improved energy efficiency.
Built for integration
Compatible with multiple energy exchange systems, with customisable material and design options.
The range
Types and configurations
Each of these is a distinct engineering answer. Tell us the duty and we'll tell you which one belongs on your plant.
Thermal energy storage tanks
Storage tailored to multi-energy system applications.
Buffer tanks
Listed among our products and services alongside pump and transfer skids.
Commercial direct hot water tanks (calorifiers)
Commercial hot water storage.
Commercial indirect water tanks
Copper coil storage tanks with an enamel-coated double coil for heat exchange efficiency and pressure resistance.
Boiler feedwater tanks
Feedwater storage for boiler plant.
Duplex 2205 stainless tanks
Duplex 2205 inner tank with polyurethane insulation, 1,000 to 5,000 L.
Specifications
From the datasheet
Figures as published on the Thermal IQ datasheet for this range — the specific model is confirmed at selection against your operating conditions.
- Listed capacities
- 1,000, 1,500, 2,000, 3,000 and 5,000 L (enamel and coil tanks); 1,000 to 5,000 L (duplex tanks)
- Construction options
- Plastic, stainless steel, enamel; pressurised or vented
- Enamel and coil tank steel
- Q345R, automated submerged arc welding (SAW)
- Enamel and coil tank pressure
- Design 1 MPa, working 0.8 MPa
- Enamel and coil tank temperature
- Design 95 °C, working 70 °C
- Coil tank heat exchanger
- Enamel-coated double copper coil (T2M), 4 to 10 m²
- Insulation
- 80 mm polyurethane foam (enamel and coil tanks); 50 to 75 mm polyurethane (duplex tanks)
- Anode
- 1.8 m magnesium anode rod
- Connections
- DN50 inlet, outlet and drain (enamel and coil tanks); 1" to 2" or flange (duplex tanks)
- Duplex tank outer shell
- Painted galvanised steel, SUS304 or PU coat
Applications
Where it's used
- HVAC and refrigeration
- Power generation
- Marine
- Process applications
- Food preparation
- Renewable energy
- Data centre cooling
Materials
- Enamel-lined Q345R steel
- Duplex 2205 stainless
- Copper coil (T2M)
- Polyurethane insulation
Manufacturing partner — Mammoth and RVG
Thermal IQ has partnered with Mammoth and RVG, internationally recognised HVAC manufacturers with extensive operations across the United States and China — combining local engineering knowledge with world-class manufacturing capability.
Questions
Water Tanks FAQs
Which types of water tank do you supply?
Thermal energy storage tanks, buffer tanks, commercial direct hot water tanks (calorifiers), commercial indirect water tanks and boiler feedwater tanks.
What sizes are available?
The listed enamel-lined and copper coil tanks come in 1,000, 1,500, 2,000, 3,000 and 5,000 L, and the duplex 2205 tanks run from 1,000 to 5,000 L.
What is a calorifier?
On our datasheet it is a commercial direct hot water tank — storage for commercial hot water.
What pressure and temperature are the enamel tanks rated for?
Design pressure 1 MPa and working pressure 0.8 MPa; design temperature 95 °C and working temperature 70 °C.
Related
Often specified alongside
Hot Water Heat Pumps — Air to Water
R134a air-to-water heat pumps from 5 to 200 kW heating capacity, for water temperatures up to 65 °C.
CO₂ Heat Pumps
R744 high temperature air-source heat pumps — water out at 40 to 95 °C, running in ambients from −35 to 45 °C.
Plate Heat Exchangers — Gasketed
Gasketed plate heat exchangers for HVAC and industrial duties, from full vacuum to 64 bar and 0 to 225 °C.
Next step
Get a selection — Water Tanks
Send the duty — flows, temperatures, fluids and pressures — and we'll return a selection sheet, drawing and price. If a different technology suits you better, we'll tell you that too.